1. Basic parameters
power supply voltage | AC 380V±20% |
Sampling voltage | AC 380V±20% |
Power frequency | 50 Hz ±5% |
Sampling current | 0~5A |
Maximum power consumption of the whole machine | 8W (depending on the power of the switching device being controlled) |
Control output contacts | twenty four Road D Type: Each DC 12V×20 mA (+12V) (output) J Type: 220V / 5A (Relay Output) |
2. Measurement accuracy
electricity Pressure | ±0.5% |
electricity flow | ±0.5% |
Active power | ±2.0% |
Reactive power | ±2.0% |
Power factor | ±1.0% |
3. Parameter Settings
Parameter name | initial value | Parameter range | Detailed Explanation |
Compensation parameters |
|
|
|
CT Transformer | 0001 | 1~2000 | default 1 In power factor mode , setting the transformation ratio switches to reactive power mode. The real-time data page will display the reactive power deficit parameter page. If the current transformer is... 500 to 5. Then the machine is set to 100 (using a ratio) |
Investment threshold | 0.95 | 0.80-1.00 | The set value represents the input threshold value. |
Removal threshold | 0.99 | 0.9 to -0.81 | The set value represents the cutoff threshold value. |
12V Output |
|
|
|
Delayed input | 010.00 | 000.02-250 | Delay time settings: such as 001.00 yes 1 Seconds, 000.02 yes 20 millisecond |
Delayed resection | 005.00 | 000.02-250 | Resection delay time setting: such as 001.00 yes 1 Seconds, 000.02 yes 20 millisecond |
Relay output |
|
|
|
Delayed input | 030 | 1-250 | Delay time settings: such as 001.00 yes 1 Second |
Delayed resection | 030 | 1-250 | Resection delay time setting: such as 001.00 yes 1 Second |
Test mode | automatic | Automatic/Manual | Switch between automatic and manual casting. |
Protection parameters |
|
| The "Enable/Disable" option after the parameter enables or disables the function. |
Overvoltage protection | 450.0 | 400-480 | Overvoltage protection: When the mains voltage exceeds the set value, the capacitor is disconnected. |
Overvoltage alarm | 425.0 | 380-460 | Overvoltage alarm: Indicates a current voltage alarm and maintains the current capacitor state. |
Undervoltage protection | 360.0 | 280-380 | Undervoltage protection: When the mains voltage is lower than the set value, the capacitor is disconnected. |
Undercurrent protection | 0100 | 50~1000 | Undercurrent protection: such as 0100 yes 100 When the current in milliamperes is less than the set value, the capacitor is disconnected. |
Voltage harmonics | 05.0 | 2~60 | Voltage harmonic protection: When the total harmonic distortion of the voltage exceeds the set value, the capacitor is disconnected. |
Current harmonics | 50 | 2-99 | Current harmonic protection: When the total harmonic distortion of the current exceeds the set value, the capacitor is disconnected. |
Capacitor Configuration |
|
|
|
Total number of paths | twenty four | 0-24 | Number of common capacitor banks: One common capacitor bank occupies 1 Groups, maximum 24 Group |
Common compensation capacitor Capacity configuration | 20.0 | 1-99 | Common compensation capacitor encoding: such as the common compensation capacitor number 1 For 15Kvar, the 2 Units digit 20 Kvar 01 - Total capacity = 15, 02 - Total capacity = 20 And so on. |
Clock settings |
|
|
|
Date |
| YY - MM - DD | Set date |
Hours, minutes, seconds |
| Hh : mm : ss | Set time |
Communication parameters |
|
|
|
Baud rate | 4800 | / | 1200 , 2400 , 4800 , 9600 |
Check bit | None | / | None , Even , Odd |
Communication address | 1 | 1-99 | Host computer communication address |