Intelligent Reactive Power Compensation Controller

JKW(Y)
The JKW Intelligent Reactive Power Compensation Controller is a new type of power distribution measurement and control equipment integrating data acquisition, reactive power compensation, and power grid parameter analysis. It is suitable for monitoring and reactive power compensation control of AC 0.4KV, 50Hz low-voltage power distribution systems.
The JKW Intelligent Reactive Power Compensation Controller uses a high-speed digital signal processor as its core, employs AC sampling, and features a 256x128 dot-matrix LCD screen as its human-machine interface. It includes power distribution monitoring, reactive power compensation, harmonic analysis, and an adaptive frequency algorithm.
Operating Conditions:
Air Temperature: Air temperature not exceeding +65℃ and not lower than -25℃.
Atmospheric Conditions: Air humidity not exceeding 90% at 20℃; higher relative humidity is permissible at lower temperatures.
Altitude: Not exceeding 2500 meters.
Environmental Conditions: The surrounding medium is free from flammability and explosion hazards, corrosive gases, conductive dust, and rain/snow erosion; the installation location must not experience severe vibration.
Interruption Functions:
1. Real-time Data Monitoring:
Voltage, Current, Power Factor
Capacitor Bank Switching Status
Active Power, Reactive Power
Total Harmonic Distortion (THD) of Voltage, Total Harmonic Distortion (THD) of Current
2. Reactive Power Compensation: The sampled physical quantity is reactive power; there is no switching oscillation. Δ-type compensation method
3. Protection functions
Features self-test reset and automatic reset functions.
Features undervoltage and overvoltage protection functions.
Features low current protection function.
Features total harmonic distortion (THD) over-limit protection function.

1. Basic parameters

power supply voltage

AC 380V±20%

Sampling voltage

AC 380V±20%

Power frequency

50 Hz ±5%

Sampling current

05A

Maximum power consumption of the whole machine

8W (depending on the power of the switching device being controlled)

Control output contacts

twenty four Road D Type: Each DC 12V×20 mA (+12V) (output)

18 Road J Type: 220V / 5A   (Relay output)

2. Measurement accuracy

Voltage

±0.5%

Current

±0.5%

Active power

±2.0%

Reactive power

±2.0%

Power factor

± 1.0%

3. Parameter Settings

Parameter name

initial value

Parameter range

Detailed Explanation

Compensation parameters

 

 

 

CT Transformer

0001

1-5000

The current transformer ratio of the incoming line cabinet: if the transformer is 500 Compare 5. Then the machine is set to 100 (using a ratio)

Investment threshold

0.95

0.80-1.00

The set value represents the input threshold value.

Removal threshold

0.99

0.9 to -0.81

The set value represents the cutoff threshold value.

Delayed input

010.00

1-250

Delay time settings: such as 1 yes 1 Second

Delayed resection

005.00

1-250

Resection delay time setting: such as 1 yes 1 Second

Overvoltage protection

450.0

400-480

Overvoltage protection: When the mains voltage exceeds a set value, the capacitor is disconnected.

Overvoltage alarm

425.0

380-460

Overvoltage alarm : Indicates a current voltage alarm; maintains the current capacitor state.

Undervoltage protection

360.0

280-380

Undervoltage protection: When the mains voltage is lower than the set value, the capacitor is disconnected.

Undercurrent protection

0100

50-1000

Undercurrent protection: such as 0100 yes 100 When the current in milliamperes is less than the set value, the capacitor is disconnected.

Harmonic protection

03.0

2-60

Voltage harmonic protection: When the total harmonic distortion of the mains voltage exceeds a set value, the capacitor is disconnected.

Control Mode

automatic

Manual/Automatic

Capacitor manual and automatic switching

 

Capacitor Configuration

 

 

 

Sub-complementary path

/

/

No points to add

Total number of paths

18

0-18

Number of common capacitor banks: One common capacitor bank occupies 1 Group, at most 18 Group

compensation capacitor capacity

/

/

 

No points to add

Common compensation capacitor capacity configuration

20.0

1-99

Common compensation capacitor encoding: such as the common compensation capacitor number 1 For 15Kvar, the 2 Units digit 20 Kvar 01 - Total capacity = 15; 02 - Total capacity = 20 And so on (each group's capacity needs to be set individually ).

 

 

 

 

Function Deactivation

/

 

 

Overvoltage protection

/

Investment/Exit

Set to enable the feature, set to disable the feature.

Overvoltage alarm

/

Investment/Exit

Set to enable the feature, set to disable the feature.

Undervoltage protection

/

Investment/Exit

Set to enable the feature, set to disable the feature.

Undercurrent protection

/

Investment/Exit

Set to enable the feature, set to disable the feature.

Harmonic protection

/

Investment/Exit

Set to enable the feature, set to disable the feature.

 

×