power supply voltage | AC 38 0V±20% |
Sampling voltage | AC 220V±20% |
Power frequency | 50Hz±2% |
Sampling current | 0A~5A |
1. Measurement accuracy
Voltage | ±1% |
Current | ±1% |
Active power | ± 2.5 % |
reactive power | ± 2.5 % |
Power factor | ±1.5% |
2. Set parameters
Parameter name | initial value | Parameter range | Detailed Explanation |
Compensation parameters |
|
|
|
CT ratio | 0001 | 1 to 2,000 | Current transformer ratio of incoming line cabinet: If the transformer ratio is 500:5, then this unit is set to 100 (using the ratio). |
Investment threshold | 0.9 2 | 0.80 ~ 1.00 | The set value represents the input threshold value. |
Removal threshold | 0.99 | 0.9 to -0.81 | The set value represents the cutoff threshold value. |
Delayed input | 010.00 | 5~ 250 | Delay time setting: e.g., 10 means 10 seconds. |
Delayed resection | 005.00 | 5~ 250 | Removal delay time setting: e.g., 5 is 5 seconds |
Overvoltage protection | 260.0 | 240 ~ 280 | Overvoltage protection: When the mains voltage exceeds a set value, the capacitor is disconnected. |
Overvoltage alarm | 2 45.0 | 220 ~ 260 | Overvoltage alarm: The current voltage alarm is displayed; the current capacitor state is maintained. |
Undervoltage protection | 2 08.0 | 170 ~ 220 | Undervoltage protection: When the mains voltage is lower than the set value, the capacitor is disconnected. |
Undercurrent protection | 0 100 | 50 ~ 1000 | Undercurrent protection: For example, 0 100 represents 100 mA . When the current is less than the set value, the capacitor is disconnected. |
Harmonic protection | 05.0 | 2 ~ 60 | Voltage harmonic protection: When the total harmonic distortion of the mains voltage exceeds a set value, the capacitor is disconnected. |
Debug mode | normal | Normal/Simulation | Switching between automatic and simulated casting. |
Wiring mode | Mixed supplement | Mixed supplementation/co-supplementation | Switch between mixed compensation and common compensation modes (pay attention to the controller wiring after switching). |
Function Deactivation | / |
|
|
Overvoltage protection | / | Investment/Exit | Set to enable the feature, set to disable the feature. |
Overvoltage alarm | / | Investment/Exit | Set to enable the feature, set to disable the feature. |
Undervoltage protection | / | Investment/Exit | Set to enable the feature, set to disable the feature. |
Undercurrent protection | / | Investment/Exit | Set to enable the feature, set to disable the feature. |
Harmonic protection | / | Investment/Exit | Set to enable the feature, set to disable the feature. |